Installation Instructions
32-Channel Analog Input Module
Quantum Series 140 AxI 05x 00sc
17
Selecting Data Format: Register 2
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 Default=0x2A92
NU NU NU NU
Data Format Group 1
Data Format Group 2
Data Format Group 3
Selecting Data Format: Register 3
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
Default=0x0205
Data Format Group 4
Range Selection Bit Pattern:
Data for Group 1 Range for Group 2
Reg 2 Bit 6 Bit 7 Description Reg 2 Bit 4 Bit 5 Description
0 0 16 Bit 0 0 16 Bit
*0 1 DVM *0 1 DVM
1 0 12 Bit 1 0 12 Bit
1 1 15 Bit 1 1 15 Bit
Range for Group 3 Range for Group 4
Reg 2 Bit 2 Bit 3 Description Reg 3 Bit 15 Bit 16 Description
0 0 16 Bit 0 0 16 Bit
*0 1 DVM *0 1 DVM
1 0 12 Bit 1 0 12 Bit
1 1 15 Bit 1 1 15 Bit
* The default data format is 10,000 DVM.