Spectrum-controls 1746sc-INO4vi Manual de usuario Pagina 28

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 48
  • Tabla de contenidos
  • SOLUCIÓN DE PROBLEMAS
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 27
18 SLC 500
Isolated Analog Output Modules
Configuring Each
Output Channel
After installing your module, you must configure each channel by setting
bit values in each configuration word. Output words 4 and 5 of the output
image file (addresses O:e.4 and O:e.5) configure channels 0–1 and 2–3,
respectively.
Channel 1 Configuration Byte
Channel 0 Configuration Byte
15
0
O:e.4
Address
Channel 3 Configuration Byte
Channel 2 Configuration Byte
O:e.5
A detailed explanation appears in the following table:
Table 9. Channel configuration word details, Output Words 4 and 5 (O:e.4 and O:e.5)
To select… Use these bit settings...
For Channel 1 (and 3) For Channel 0 (and 2)
Bit: 15 14 13 12 11 10 9 8 7654 3210
Output channel disable 0 0
Output channel enable 1 1
±10 Vdc output range (-INO4vi only) 0 0 0 0 0 0
1–5 Vdc output range (-INO4vi only) 0 0 1 0 0 1
0–5 Vdc output range (-INO4vi only) 0 1 0 0 1 0
0–10 Vdc output range (-INO4vi only) 0 1 1 0 1 1
0–20 mA output range 1 0 0 1 0 0
4–20 mA output range 1 0 1 1 0 1
0–21 mA output range 1 1 0 1 1 0
Invalid 1 1 1 1 1 1
Engineering units 0 0 0 0 0 0
Scaled for PID 0 0 1 0 0 1
Proportional counts 0 1 0 0 1 0
1746-NO4 compatible format 0 1 1 0 1 1
User-defined scale 1 1 0 1 1 0
Invalid 1 0 0 1 0 0
Invalid 1 0 1 1 0 1
Invalid 1 1 1 1 1 1
Reset output on fault 0 0
Hold last value on fault 1 1
Vista de pagina 27
1 2 ... 23 24 25 26 27 28 29 30 31 32 33 ... 47 48

Comentarios a estos manuales

Sin comentarios