18 SLC 500
™
Isolated Analog Output Modules
Configuring Each
Output Channel
After installing your module, you must configure each channel by setting
bit values in each configuration word. Output words 4 and 5 of the output
image file (addresses O:e.4 and O:e.5) configure channels 0–1 and 2–3,
respectively.
Channel 1 Configuration Byte
Channel 0 Configuration Byte
15
0
O:e.4
Address
Channel 3 Configuration Byte
Channel 2 Configuration Byte
O:e.5
A detailed explanation appears in the following table:
Table 9. Channel configuration word details, Output Words 4 and 5 (O:e.4 and O:e.5)
To select… Use these bit settings...
For Channel 1 (and 3) For Channel 0 (and 2)
Bit: 15 14 13 12 11 10 9 8 7654 3210
Output channel disable 0 0
Output channel enable 1 1
±10 Vdc output range (-INO4vi only) 0 0 0 0 0 0
1–5 Vdc output range (-INO4vi only) 0 0 1 0 0 1
0–5 Vdc output range (-INO4vi only) 0 1 0 0 1 0
0–10 Vdc output range (-INO4vi only) 0 1 1 0 1 1
0–20 mA output range 1 0 0 1 0 0
4–20 mA output range 1 0 1 1 0 1
0–21 mA output range 1 1 0 1 1 0
Invalid 1 1 1 1 1 1
Engineering units 0 0 0 0 0 0
Scaled for PID 0 0 1 0 0 1
Proportional counts 0 1 0 0 1 0
1746-NO4 compatible format 0 1 1 0 1 1
User-defined scale 1 1 0 1 1 0
Invalid 1 0 0 1 0 0
Invalid 1 0 1 1 0 1
Invalid 1 1 1 1 1 1
Reset output on fault 0 0
Hold last value on fault 1 1