Compact IO™ Isolated HART Analog Output Module
User’s Manual 0300217-03 Rev. A
9-4
Table 9-3 (Module Error Types)
Error Type Module Error
Fie ld Value Bits
11 through 9
(binary)
Description
No errors 000 No error is present. The extended error field holds no
additional information.
Hardw are
Errors
001 General and specific hardw are error codes are
specified in the extended error information field.
Configuration
Errors
010 Module-specific error codes are indicated in the
extended error field. These error codes correspond to
options that you can change directly. For example, the
input range or input filter selection.
9.6.2 Extended Error Information Field
Check the extended error information field when a non-zero value is present in the
module error field. Depending upon the value in the module error field, the extended
error information field can contain error codes that are module-specific or common to all
1769 analog modules.
Note: If no errors are present in the module error field, the extended error
information field is set to zero.
Hardware Errors
General or module-specific hardware errors are indicated by module error code 001. See
Table 9-4 (Extended Fault Codes).
Configuration Errors
If you set the fields in the configuration file to invalid or unsupported values, the module
generates a critical error.
Table 9-4 (Extended Fault Codes) lists the possible module-specific configuration error
codes defined for the module.