Spectrum-controls 1769sc-IF8u Manual de usuario Pagina 71

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 126
  • Tabla de contenidos
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 70
Chapter 5: Diagnostics and Troubleshooting 61
Module Error
Definition Table
Analog module errors are expressed in two fields as four-digit Hex format
with the most significant digit as “don’t care” and irrelevant. The two
fields are “Module Error” and “Extended Error Information”. The
structure of the module error data is shown below.
Table 5.1 Module Error Table
1514131211109876543210
0000000000000000
"Don't Care" Bits Module Error Extended Error Information
He x Digit 4 He x Digit 3 Hex Digit 2 He x Digit 1
Module Error Field
The purpose of the module error field is to classify module errors into
three distinct groups, as described in the table below. The type of error
determines what kind of information exists in the extended error
information field. These types of module errors are typically reported in
the controllers I/O status file. Refer to your controller manual for details.
Table 5.2 Module Error Types
Error Type Module Error
Field Value Bits
11 through 9
(binary)
Description
No errors 000 No error is present. The extended error field holds no
additional information.
Har dw ar e
Errors
001 General and specific hardware error codes are
specified in the extended error information field.
Conf iguration
Er r o r s
010 Module-specific error codes are indicated in the
extended error field. These error codes correspond to
options that you can change directly. For example, the
input range or input filter selection.
Extended Error Information Field
Check the extended error information field when a non-zero value is
present in the module error field. Depending upon the value in the module
Vista de pagina 70
1 2 ... 66 67 68 69 70 71 72 73 74 75 76 ... 125 126

Comentarios a estos manuales

Sin comentarios

Kingston Technology Karty pamięci podręczniki użytkownika

Zaczynanie od C

Kliknij na poniższy alfabet, aby przejść do pełnej listy modeli zaczynających się od tej litery

Modele Rodzaj dokumentu
CF/1024
Arkusz Danych   Kingston Technology 1GB Standard CompactFlash Card, 1 strony
CF/1GB
Arkusz Danych   Kingston Technology CompactFlash 1GB, 1 strony
CF/2GB-U
Arkusz Danych   Kingston Technology 2GB CompactFlash Card Ultimate 100x, 2 strony