3-10 Chapter 3: Configuring the Module
User’s Manual Pub. 0300272-01 Rev. A.0
The New Module dialog appears:
View or specify the following options:
Name. Enter name of new module.
Description. If needed, enter a description for the module.
Comm Format. Select the communication format. When you select a
communication format, you are also selecting the configuration formats
for the module. For an OE2CIH module, select Data INT.
Slot. Enter the slot number in which the module resides.
Connection Parameters. For the OE2CIH module, use the following
parameters:
- Input. Enter 101 for the Assembly Instance. Enter 28 for the
Size.
- Output. Enter 102 for the Assembly Instance. Enter 3 for the
Size.
- Configuration. Enter 225 for the Assembly Instance. Enter 40
for the Size.
The Module Properties Connection tab appears. Make any
changes necessary, and then click OK to exit the window.