Spectrum-controls 1734sc-OE2CIH Manual de usuario Pagina 64

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 74
  • Tabla de contenidos
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 63
4-28 Chapter 4: OE2CIH and HART
User’s Manual Pub. 0300272-01 Rev. A.0
Request Data
Resume Normal HART acquisitions - Request packet structure
Request Size = 0
Offset
Field
Value
Definition
0
No Request Data
Reply Data
Resume Normal HART acquisitions - Reply packet structure
Reply Size = 2 bytes
Offset
Field
Value
Definition
0
Status
(1 byte)
00 = SUCCESS
35 = DR_DEAD
1
Pad
0
Table 4-21 Get Channel(s) Device Status (Service Code = 0×62)
Unconnected Message
Field
Value
Definition
Message Type
CIP Generic
Service Code
62
Get Device Status
Class Name
035D
HART Object
Instance
0 = All Channels
1 to n = Single Channel (n-1)
All channels at once
or a single channel
Object Attribute
None, leave this field blank
Request Size
0
No Request Data
Reply Size
12–Single Channels Device Status
(12*n)–All Channels Device Status
Number of Data
bytes returned
Request Data
Get Single Channel Device - Request packet structure
Request Size = 0
Offset
Field
Value
Definition
No Request Data
Vista de pagina 63
1 2 ... 59 60 61 62 63 64 65 66 67 68 69 ... 73 74

Comentarios a estos manuales

Sin comentarios