Installing And Wiring Your Module
Read this chapter to install and wire your module. This chapter covers:
avoiding electrostatic damage
determining power requirements
installing the module
wiring signal cables to the module’s terminal block
Electrostatic
Damage
Electrostatic discharge can damage semiconductor devices inside this
module if you touch backplane connector pins. Guard against
electrostatic damage by observing the following precautions:
CAUTION
ELECTROSTATICALLY SENSITIVE COMPONENTS
• Before handling the module, touch a grounded
object to rid yourself of electrostatic charge.
• When handling the module, wear an approved wrist strap
grounding device.
• Handle the module from the front, away from the
backplane connector. Do not touch backplane connector pins.
• Keep the module in its static-shield container when not in use or
during shipment.
Failure to observe these precautions can degrade the module’s
performance or cause permanent damage.
Power
Requirements
The module receives its power through the ControlLogix chassis
backplane from the fixed or modular +5 VDC and +24 VDC chassis
power supply. The maximum current drawn by the module is shown in
the table below.
Table 2.1. Maximum current drawn by the module
5VDC Amps 24VDC Amps
0.230 0.075