Chapter 6: 1756sc-OF8H Channel Configuration, Data, and Status 59
Table 6.2b
Tag Name Data Type Style Description
Of8h0Input.ModuleStatus.16 BOOL DEC Channel 0 HART out-of-service
0 = In service
1 = Out-of-service
Of8h0Input.ModuleStatus.17 BOOL DEC Channel 1 HART out-of-service
0 = In service
1 = Out-of-service
Of8h0Input.ModuleStatus.18 BOOL DEC Channel 2 HART out-of-service
0 = In service
1 = Out-of-service
Of8h0Input.ModuleStatus.19 BOOL DEC Channel 3 HART out-of-service
0 = In service
1 = Out-of-service
Of8h0Input.ModuleStatus.20 BOOL DEC Channel 4 HART out-of-service
0 = In service
1 = Out-of-service
Of8h0Input.ModuleStatus.21 BOOL DEC Channel 5 HART out-of-service
0 = In service
1 = Out-of-service
Of8h0Input.ModuleStatus.22 BOOL DEC Channel 6 HART out-of-service
0 = In service
1 = Out-of-service
Of8h0Input.ModuleStatus.23 BOOL DEC Channel 7 HART out-of-service
0 = In service
1 = Out-of-service
Of8h0Input.ModuleStatus.24 BOOL DEC Unused
Of8h0Input.ModuleStatus.25 BOOL DEC Calibration fault
0 = No fault
1 = Fault
Of8h0Input.ModuleStatus.26 BOOL DEC Calibration in progress
0 = Calibration NOT active
1 = Calibrating
Of8h0Input.ModuleStatus.27 BOOL DEC Unused
Of8h0Input.ModuleStatus.28 BOOL DEC Unused
Of8h0Input.ModuleStatus.29 BOOL DEC Unused
Of8h0Input.ModuleStatus.30 BOOL DEC Unused
Of8h0Input.ModuleStatus.31 BOOL DEC Analog group fault
0 = No fault
1 = Fault