Selecting Input Ranges: Register 1
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 Default=0x2000 (0x2924 for 140 ACI 050sc)
NU NU Input Range Group 1
Input Range Group 2
Input Range Group 3
Input Range Group 4
Range Selection Bit Pattern:
Range for Group 1 Range for Group 2
Bit 14 Bit 15 Bit 16 Description Bit 11 Bit 12 Bit 13 Description
*0 0 0 -10V to +10V *0 0 0 -10V to +10V
0 0 1 +1V to +5V 0 0 1 +1V to +5V
0 1 0 0V to +5V 0 1 0 0V to +5V
0 1 1 0V to +10V 0 1 1 0V to +10V
*1 0 0 0 to 20mA *1 0 0 0 to 20mA
1 0 1 4 to 20mA 1 0 1 4 to 20mA
1 1 0 Not valid 1 1 0 Not valid
1 1 1 Not valid 1 1 1 Not valid
Range for Group 3 Range for Group 4
Bit 8 Bit 9 Bit 10 Description Bit 5 Bit 6 Bit 7 Description
*0 0 0 -10V to +10V *0 0 0 -10V to +10V
0 0 1 +1V to +5V 0 0 1 +1V to +5V
0 1 0 0V to +5V 0 1 0 0V to +5V
0 1 1 0V to +10V 0 1 1 0V to +10V
*1 0 0 0 to 20mA *1 0 0 0 to 20mA
1 0 1 4 to 20mA 1 0 1 4 to 20mA
1 1 0 Not valid 1 1 0 Not valid
1 1 1 Not valid 1 1 1 Not valid
* The default range is 0 to 20 mA for the 140 ACI 050sc current only module. Otherwise it is -
10V to +10V
17
Installation Instructions
32-Channel Analog Input Module
Quantum Series 140 ACI 052 00sc