Chapter 4
MODULE CONFIGURATION AND STATUS
The 140 ACI 052 00sc uses a total of nine 3x level and nine 4x level registers.
After Modsoft (Section 2.3) or Concept (Section 3.3) software is installed,
additional configuration and status registers are set as follows:
4.1 Configuration word format (Register 4x)
1 2 3 4 5 6 7 8 9 10 111213141516
Select a group
Mode Select
Autosequence Disable
Reserved
Disable channel 1-4
Disable channel 5-8
Disable channel 9-12
Disable channel 13-16
Disable channel 17-20
Disable channel 21-24
Disable channel 25-28
Disable channel 29-32
4x Group Channel Disable: Bits 1-8
These bits are used to fine tune the response time of your system. They enable
data acquisition on eight groups of four channels each. A 0 enables the group,
a 1 disables the group. Disabling groups of channels improves system response
time.
27
Installation Instructions
32-Channel Analog Input Module
Quantum Series 140 ACI 052 00sc