4.4 Channel Status (Registers 3x+ 0 through 3x+7)
As described in Section 2.5, register 4x bits 1and 2 can be set to allow
monitoring of individual channel status (set to 0 and 1
respectively). You will then be displaying eight channels of status
information. As described below, bits 1-4 provide four different
pieces of error information specific to that input channel. Bits 5-11
merely confirm what setup has been created for that feature in
configuration register 4x. Bits 12-16 will indicate what channels
status is being displayed.
Channel Status Register:
1 2 3 4 5 6 7 8 9 10 111213141516
Channel Number
Filter Selection
Input Data Format
Range Selected
Under range
Over range
Configuration error
Calibration error
3x+0 . . . 7 Calibration Error Flag: Bit 1
The calibration error flag is a fatal error. When the flag is set to 1
the ADC cannot calibrate within specifications.
3x+0 . . . 7 Configuration Error Flag: Bit 2
The calibration error flag is a fatal error. When the flag is set to 1
there is a configuration mismatch. Configuration errors include any
illegal configuration, such the selection of an unsupported format or
filter option, or configurations that must be the same for all channels
within a group of channels.
3x+0 . . . 7 Over Range Flag: Bit 3
This is a nonfatal over range flag. The bit is set to 1 when an input
value is read within one count of the maximum range value. When
the input value is within normal limits the flag is automatically reset
to 0.