1-2 Compact™ IO Isolated RTD/Resistance Module
User’s Manual Pub. 0300241-01 Rev. A
1.1.1 RTD/Resistance Inputs and Ranges
The table below lists the RTD and resistance types and their associated full-scale ranges,
supported by the IR6I module.
Input Type
Input Range
˚ Celsius
Fahrenheit
Pt 385 -200 to +850 -328 to 1562
Pt 3916 -200 to +630 -328 to 1166
10 Cu 426 -100 to +260 -148 to 500
100 Ni 618 -100 to +260 -148 to 500
120 Ni 672 -80 to +260 -112 to 500
604 NiFe 518 -100 to +200 -148 to 392
150 ohm 0 to +1500
1
500 ohm 0 to +500
1
1000 ohm 0 to +1000
1
3000 ohm 0 to +3000
1
1.1.2 Data Formats
The data can be configured on board each module as:
• Engineering units x 1
• Engineering units x 10
• Scaled-for-PID
• Percent of full-scale
• Raw/proportional data
1.1.3 Filter Frequencies
The module uses a digital filter that provides high frequency noise rejection for the input
signals. The filter is programmable, allowing you to select from six different filter
frequencies for each channel:
• 4.17 Hz
• 10 Hz
• 16.7 Hz
• 19.6 Hz
• 62 Hz
• 470 Hz
Comentarios a estos manuales