5-6 Compact™ IO Isolated RTD/Resistance Module
User’s Manual Pub. 0300241-01 Rev. A
Error Type
Hex
Equivalent
Module
Error
Code
(Binary)
Extended Error
Information Code
(Binary)
Error Description
X414 010 0 0001 0100 An unused bit has been set for ch1 (C:e.1)
X415 010 0 0001 0101 An unused bit has been set for ch2 (C:e.2)
X416 010 0 0001 0110 An unused bit has been set for ch3 (C:e.3)
X417 010 0 0001 0111 An unused bit has been set for ch4 (C:e.4)
X418 010 0 0001 1000 An unused bit has been set for ch5 (C:e.5)
X419 010 0 0001 1001 An unused bit has been set for Module Configuration Register
(C:e.6)
Section 5.8
Module Inhibit
Function
Some controllers support the module inhibit function. See your controller manual for
details.
Whenever the 1769sc-IR6I module is inhibited, the module continues to provide
information about changes at its inputs to the 1769 CompactBus master (for example, a
CompactLogix controller).