Compact IO™ Isolated HART Analog Input Module
User's Manual 0300215-03 Rev. A
6-10
Figure 6-2 (Frequency Response)
The cut-off frequency for each channel is defined by its filter frequency selection. Choose
a filter frequency so that your fastest changing signal is below that of the filter’s cut-off
frequency. The cut-off frequency should not be confused with the update time. The cut-
off frequency relates to how the digital filter attenuates frequency components of the
input signal.
The update time defines the rate at which an input channel is scanned and its channel data
word is updated.
28.5Hz Filter
-120
-100
-80
-60
-40
-20
0
0102030405060708090
Filter Rejection (dB)
50 Hz Filter
-120
-100
-80
-60
-40
-20
0
0 20 40 60 80 100 120 140 160
Filter Rejection (dB)
60Hz Filter Operation
-120
-100
-80
-60
-40
-20
0
0 50 100 150 200
Filter Rejection (dB)
300Hz Filter Oper ation
-120
-100
-80
-60
-40
-20
0
0 200 400 600 800 1000
Filter Rejection (dB)
360Hz Filter Operation
-120
-100
-80
-60
-40
-20
0
0 200 400 600 800 1000 1200
Filter Rejection (dB)