Chapter 4: Module Data, Status, and Configuration
User's Manual 0300215-03 Rev. A
6-17
Section 6.6
Determining
Effective
Resolution
and Range
The effective resolution for an input channel depends upon the filter frequency selected
for that channel. The following tables provide the effective resolution for each of the
range selections at the six available frequencies. The tables do not include the affects of
unfiltered input noise. Choose the frequency that most closely matches your
requirements.
Table 6-10 (Effective Resolution)
Range Filter (Hz) Channel Input Value Measured
Max
Deviation
+/-10V 28.5 0 5.0V 1
+/-10V 50 1 5.0V 1
+/-10V 60 2 5.0V 1
+/-10V 300 3 5.0V 3
+/-10V 360 0 5.0V 3
0-10V 28.5 1 5.0V 1
0-10V 50 2 5.0V 1
0-10V 60 3 5.0V 1
0-10V 300 0 5.0V 5
0-10V 360 1 5.0V 8
0-5V 28.5 2 2.5V 1
0-5V 50 3 2.5V 1
0-5V 60 0 2.5V 1
0-5V 300 1 2.5V 11
0-5V 360 2 2.5V 12
1-5V 28.5 3 3.0V 1
1-5V 50 0 3.0V 1
1-5V 60 1 3.0V 1
1-5V 300 2 3.0V 9
1-5V 360 3 3.0V 26
0-20mA 28.5 0 10mA 1
0-20mA 50 1 10mA 3
0-20mA 60 2 10mA 1
0-20mA 300 3 10mA 13
0-20mA 360 0 10mA 16
4-20mA 28.5 1 10mA 1
4-20mA 50 2 10mA 1
4-20mA 60 3 10mA 1
4-20mA 300 0 10mA 13
4-20mA 360 1 10mA 20